Very cool and interesting, the Fieldpiece SDP2 is the first psychrometer designed for HVAC/R work that can display and show a change in enthalpy. Coupled with an accurate airflow instrument like the Fieldpiece STA2, field capacity in BTUh and even field EER can easily be calculated. The SDP2 uses capacitive electric humidity sensors and thermistor technology to accurately determine all of the psychrometric readings assuring a high level of accuracy and repeatability during the process.

The SDP2 Dual In-Duct Psychrometer is more than just your everyday HVACR psychrometer. It gives HVACR professionals more insight into HVAC evaporator performance than any other psychrometer, because it takes four evaporator measurements at one time: supply wet bulb, supply dry bulb, return wet bulb, and return dry bulb.

HVACR professionals get a live, real-time snap shot of the evaporator performance, even while conditions are changing. Based on these live, dynamic readings, the SDP2 Dual In-Duct Psychrometer registers system changes as they happen, and automatically calculates actual Delta-T, Target Delta-T, actual Evaporator Exit Temperature, and Target Evaporator Exit Temperature. Plus enthalpy (BTU/LBM) and Dew Point can be displayed in real-time.

* The SDP2 is a great tool to help HVACR professionals do more all by itself. But couple it with the JL2 and then to the JobLink APP and your work improves dramatically in an instant. Not only are you checking and servicing a unit based on live real-time measurements, but the wireless communication lets you be in two or more places at one time!

Características:

  • Sends live indoor wet bulb readings directly to the SMAN460 wireless manifold or via JL2 Transmitter to the Fieldpiece Job Link App
    • The SDP2 does not link wirelessly with the new SM380V and SM480V (released in 2019). The new SM380V and SM480V manifolds accept wireless measurements from the Job Link Probes for air measurements.
  • Real-time Target Evaporator Exit Temperature and Target Delta T
  • Displays actual indoor unit performance, AND calculates how indoor unit should be performing
  • Shows enthalpy change across the evaporator -- in real-time
  • Wirelessly sends all 4 evaporator temperatures to the JobLink APP via the JL2 accessory for full system diagnostics

Plus:

  • Hands-free testing
  • Bright backlight
  • Threaded probe locks
  • Ruled, 38" telescoping probes
  • Magnetic hanger
  • Rugged design
  • Dual display

Características técnicas

  • Telescoping probe length: Up to 38 inches (97cm)
  • Probe tip diameter: 0.35 inch (9mm)
  • Storage temperature: -4°F to 140°F (-20°C to 60°C), 0 to 80% RH (with battery removed)
  • Temperature coefficient: 0.1 x (specified accuracy)/°C (<18°C or >28°C)
  • Over range: "OL" or "-OL" is displayed
  • Power: Single standard 9-volt battery, NEDA 1604, JIS 006P, IEC 6F22
  • Auto power off: after 30 minutes of inactivity if APO is active.
  • Battery life: Approx. 120 hours standard use (alkaline
  • Low battery indication: is displayed when the battery voltage drops below the operating level.
  • Dimensions: 7.9 in (H) x 2.6 in (W) x 1.4 in (D), [200mm (H) x 66mm (W) x 36mm (D)]
  • Weight: Approx. 570g, including battery

Temperatura

  • Sensor type: Precision thermistor
  • Operating environment: -4°F to 140°F (-20°C to 60°C)
  • Range: -4°F to 140°F (-20°C to 60°C)
  • Resolution: 0.1°F / 0.1°C
  • Accuracy: ±(1°F) 32°F to 113°F ±(2°F) -4°F to 32°F, 113°F to 140°F ±(0.5°C) 0°C to 45°C ±(1°C) -20°C to 0°C, 45°C to 60°C

Relative Humidity:

  • Sensor type: Capacitance polymer film
  • Operating environment: 32°F to 131°F (0°C to 55°C)
  • Range: 0% to 100%RH
  • Accuracy: ±(2.5%) 10% to 90%RH ±(5%) <10%RH and >90%RH Note: Above accuracies stated at 73.4°F (23°C).
  • Sensor response time: 60 seconds typical for 90% of total range.
  • Sensor hysteresis: ±1%RH typical (Excursion of 10% to 90% to 10%RH)

Wireless:

  • Frequency range: 910MHz ~ 920MHz
  • FCC ID: VEARF915
  • Range: 100 feet
  • Minimum Wireless Range: 1 foot (30cm)

Error Codes

You may see an error code in TEET or Target Delta T mode. Usually it means probes are swapped or a bad sensor (model RSDP2).

  • Err 01: Return wet bulb is higher than dry bulb.
  • Err 02: Return wet bulb is extremely low.
  • Err 03: Supply dry bulb is higher than return dry bulb.
  • Err 04: Return values are outside calculating range.
  • Err 05: Supply values are outside calculating range.
  • Err 06: Both the return and supply values are outside calculating range.

(Err 04, 05, 06 supersedes Err 01, 02, 03)